Is fine stranded wire ok for main supply line?





.everyoneloves__top-leaderboard:empty,.everyoneloves__mid-leaderboard:empty,.everyoneloves__bot-mid-leaderboard:empty{ margin-bottom:0;
}







6















I’m changing the load panel in a mobile home with additions to gain additional circuits.



Outside a few feet from home is the service pole with meter and a 100 amp disconnect.



I became concerned about the entrance wire because it is a fine stranded wire like automotive battery cables or like welding equipment wiring. The picture shows the work in progress and it is complete now but I wonder if this type wire is anything to be concerned about especially since I will be adding to the load draw with a central heat pump.



enter image description here



In the red square you can sort of see the fine strands that the entrance wire has. I can’t get better pictures until I return to this vacation home.



To clarify I was expecting the wire to be stranded like this
enter image description here



But what I have is very similar to this



enter image description here










share|improve this question

























  • When you get back there, can you get us better pictures, especially showing any markings that are present on those feeder wires?

    – ThreePhaseEel
    Mar 31 at 20:10











  • Also, would you be able to get us a very close-up of the end of a representative wire? Your photo doesn't show nearly enough to let me count strands...

    – ThreePhaseEel
    Mar 31 at 20:20











  • @ThreePhaseEel yes I will edit in better pictures in a week or so. In your experience have you seen very finely stranded wire used fir this application?

    – Kris
    Mar 31 at 21:27











  • it's not common for sure, and if it was fine stranded, then it's a 110.3 labeling/listing vio as loadcenter lugs aren't listed to accept it, but it's definitely possible

    – ThreePhaseEel
    Mar 31 at 22:10











  • I see Mr. Snippy has been in the panel and cut back all but the minimum possible wire length. Better to leave enough length to allow hot+neutral to reach any space in the panel. Neutral too because GFCI+AFCI.

    – Harper
    Mar 31 at 23:21


















6















I’m changing the load panel in a mobile home with additions to gain additional circuits.



Outside a few feet from home is the service pole with meter and a 100 amp disconnect.



I became concerned about the entrance wire because it is a fine stranded wire like automotive battery cables or like welding equipment wiring. The picture shows the work in progress and it is complete now but I wonder if this type wire is anything to be concerned about especially since I will be adding to the load draw with a central heat pump.



enter image description here



In the red square you can sort of see the fine strands that the entrance wire has. I can’t get better pictures until I return to this vacation home.



To clarify I was expecting the wire to be stranded like this
enter image description here



But what I have is very similar to this



enter image description here










share|improve this question

























  • When you get back there, can you get us better pictures, especially showing any markings that are present on those feeder wires?

    – ThreePhaseEel
    Mar 31 at 20:10











  • Also, would you be able to get us a very close-up of the end of a representative wire? Your photo doesn't show nearly enough to let me count strands...

    – ThreePhaseEel
    Mar 31 at 20:20











  • @ThreePhaseEel yes I will edit in better pictures in a week or so. In your experience have you seen very finely stranded wire used fir this application?

    – Kris
    Mar 31 at 21:27











  • it's not common for sure, and if it was fine stranded, then it's a 110.3 labeling/listing vio as loadcenter lugs aren't listed to accept it, but it's definitely possible

    – ThreePhaseEel
    Mar 31 at 22:10











  • I see Mr. Snippy has been in the panel and cut back all but the minimum possible wire length. Better to leave enough length to allow hot+neutral to reach any space in the panel. Neutral too because GFCI+AFCI.

    – Harper
    Mar 31 at 23:21














6












6








6








I’m changing the load panel in a mobile home with additions to gain additional circuits.



Outside a few feet from home is the service pole with meter and a 100 amp disconnect.



I became concerned about the entrance wire because it is a fine stranded wire like automotive battery cables or like welding equipment wiring. The picture shows the work in progress and it is complete now but I wonder if this type wire is anything to be concerned about especially since I will be adding to the load draw with a central heat pump.



enter image description here



In the red square you can sort of see the fine strands that the entrance wire has. I can’t get better pictures until I return to this vacation home.



To clarify I was expecting the wire to be stranded like this
enter image description here



But what I have is very similar to this



enter image description here










share|improve this question
















I’m changing the load panel in a mobile home with additions to gain additional circuits.



Outside a few feet from home is the service pole with meter and a 100 amp disconnect.



I became concerned about the entrance wire because it is a fine stranded wire like automotive battery cables or like welding equipment wiring. The picture shows the work in progress and it is complete now but I wonder if this type wire is anything to be concerned about especially since I will be adding to the load draw with a central heat pump.



enter image description here



In the red square you can sort of see the fine strands that the entrance wire has. I can’t get better pictures until I return to this vacation home.



To clarify I was expecting the wire to be stranded like this
enter image description here



But what I have is very similar to this



enter image description here







electrical wiring






share|improve this question















share|improve this question













share|improve this question




share|improve this question








edited Apr 1 at 12:58







Kris

















asked Mar 31 at 18:44









KrisKris

1,0191611




1,0191611













  • When you get back there, can you get us better pictures, especially showing any markings that are present on those feeder wires?

    – ThreePhaseEel
    Mar 31 at 20:10











  • Also, would you be able to get us a very close-up of the end of a representative wire? Your photo doesn't show nearly enough to let me count strands...

    – ThreePhaseEel
    Mar 31 at 20:20











  • @ThreePhaseEel yes I will edit in better pictures in a week or so. In your experience have you seen very finely stranded wire used fir this application?

    – Kris
    Mar 31 at 21:27











  • it's not common for sure, and if it was fine stranded, then it's a 110.3 labeling/listing vio as loadcenter lugs aren't listed to accept it, but it's definitely possible

    – ThreePhaseEel
    Mar 31 at 22:10











  • I see Mr. Snippy has been in the panel and cut back all but the minimum possible wire length. Better to leave enough length to allow hot+neutral to reach any space in the panel. Neutral too because GFCI+AFCI.

    – Harper
    Mar 31 at 23:21



















  • When you get back there, can you get us better pictures, especially showing any markings that are present on those feeder wires?

    – ThreePhaseEel
    Mar 31 at 20:10











  • Also, would you be able to get us a very close-up of the end of a representative wire? Your photo doesn't show nearly enough to let me count strands...

    – ThreePhaseEel
    Mar 31 at 20:20











  • @ThreePhaseEel yes I will edit in better pictures in a week or so. In your experience have you seen very finely stranded wire used fir this application?

    – Kris
    Mar 31 at 21:27











  • it's not common for sure, and if it was fine stranded, then it's a 110.3 labeling/listing vio as loadcenter lugs aren't listed to accept it, but it's definitely possible

    – ThreePhaseEel
    Mar 31 at 22:10











  • I see Mr. Snippy has been in the panel and cut back all but the minimum possible wire length. Better to leave enough length to allow hot+neutral to reach any space in the panel. Neutral too because GFCI+AFCI.

    – Harper
    Mar 31 at 23:21

















When you get back there, can you get us better pictures, especially showing any markings that are present on those feeder wires?

– ThreePhaseEel
Mar 31 at 20:10





When you get back there, can you get us better pictures, especially showing any markings that are present on those feeder wires?

– ThreePhaseEel
Mar 31 at 20:10













Also, would you be able to get us a very close-up of the end of a representative wire? Your photo doesn't show nearly enough to let me count strands...

– ThreePhaseEel
Mar 31 at 20:20





Also, would you be able to get us a very close-up of the end of a representative wire? Your photo doesn't show nearly enough to let me count strands...

– ThreePhaseEel
Mar 31 at 20:20













@ThreePhaseEel yes I will edit in better pictures in a week or so. In your experience have you seen very finely stranded wire used fir this application?

– Kris
Mar 31 at 21:27





@ThreePhaseEel yes I will edit in better pictures in a week or so. In your experience have you seen very finely stranded wire used fir this application?

– Kris
Mar 31 at 21:27













it's not common for sure, and if it was fine stranded, then it's a 110.3 labeling/listing vio as loadcenter lugs aren't listed to accept it, but it's definitely possible

– ThreePhaseEel
Mar 31 at 22:10





it's not common for sure, and if it was fine stranded, then it's a 110.3 labeling/listing vio as loadcenter lugs aren't listed to accept it, but it's definitely possible

– ThreePhaseEel
Mar 31 at 22:10













I see Mr. Snippy has been in the panel and cut back all but the minimum possible wire length. Better to leave enough length to allow hot+neutral to reach any space in the panel. Neutral too because GFCI+AFCI.

– Harper
Mar 31 at 23:21





I see Mr. Snippy has been in the panel and cut back all but the minimum possible wire length. Better to leave enough length to allow hot+neutral to reach any space in the panel. Neutral too because GFCI+AFCI.

– Harper
Mar 31 at 23:21










4 Answers
4






active

oldest

votes


















4














A terminal problem



Beyond the potential labeling/marking (or lack thereof) issues with this wire, there is a serious problem with this setup: equipment terminal lugs are not suited for fine stranded wire (anything finer than what UL calls Class C stranding) unless the equipment is specifically listed for use with specific fine strandings, which is not true for light duty loadcenters.



As a result, what we have right now is a 110.3 violation of the loadcenter's listing and labeling, atop anything else that's going on with the wire itself. Given that the wire appears to be in conduit, simply replacing the run with the correct stuff is the best option, as that will cure any issues with labeling/marking as well, and also gives you the chance to adjust conductor sizing as-needed.






share|improve this answer
























  • Thank you I was not comfortable with how the lug was capturing the soft bundle of strands now I am certain I will change the cable .

    – Kris
    Apr 2 at 1:51











  • +1 This is the best answer to the headline question and is most likely to help others with the same question in the future.

    – statueuphemism
    Apr 2 at 14:10



















7














I can call it right now.



I don't see any markings on the wires. Now, perhaps the wires come out of a multiconductor cable, whose cable sheath has markings that indicate it is one of the NEC/UL rated types of wire legal for mains wiring. But if not...



Wires without insulation markings are no wires at all.



You don't even know what you're looking at here. You don't know what insulation temp column you should be pulling out of for 310.15(B)(16). You don't know if it's 600V insulation. We don't know if the insulation will hold up over time, in the environmental conditions, or with the heat of the wires working normally. For all we know it could be Chinese car battery cable.



Given that it's all 4 colors, there's a fair chance it's cable in sheath, or was shucked from cable in sheath (there go the markings). This is why you can't shuck NM to get wires for running in conduit.






share|improve this answer



















  • 1





    We do know it has held up over time since the original setup of mobile home was in 1969. What I don’t know is if it will hold up in the future with a heat pump being added to the mix. There was no ac in this house only a small electric furnace which was rarely used since it is a summer destination. I’m thinking I will replace the short run from outside disconnect to panel.

    – Kris
    Mar 31 at 23:47











  • Is there an NEC/UL rated wire that is fine stranded and legal for use as service entrance cable?

    – Kris
    Mar 31 at 23:58



















1














Yes there is fine stranded wire, it is not common because it is more expensive. I use it on equipment that has a high vibration or regular movement because the fine wire holds up better in those conditions than heavier strands. thick strands tend to break with movement. Since this is a mobile that might be why this type wire was used but it goes back to the size of the wire if it will do the job or not, fine or heavy strands don't matter it's the gauge or size that is the limiting factor.






share|improve this answer
























  • I’m thinking grand dad who had a big woodworking shop with some large three phase machines may have used some reclaimed wire here. I will verify the size of the wire before final decision is made to replace or not.

    – Kris
    Apr 1 at 14:29



















1














I won't comment on the legalities since I'm not from the US and I'm not deeply familiar with their codes, but from a safety point of view my big concern would be the insulation.



It's difficult to be 100% sure from a photo but those conductors look like rubber to me. Rubber insulation was phased out from fixed-wiring wires/cables a long time ago, but it's still used to this day on some types of flexible cord.



The problem with rubber is it can oxidise over time leading it to harden, then when the cables are manipulated to modify the installation it can crack.






share|improve this answer
























    Your Answer








    StackExchange.ready(function() {
    var channelOptions = {
    tags: "".split(" "),
    id: "73"
    };
    initTagRenderer("".split(" "), "".split(" "), channelOptions);

    StackExchange.using("externalEditor", function() {
    // Have to fire editor after snippets, if snippets enabled
    if (StackExchange.settings.snippets.snippetsEnabled) {
    StackExchange.using("snippets", function() {
    createEditor();
    });
    }
    else {
    createEditor();
    }
    });

    function createEditor() {
    StackExchange.prepareEditor({
    heartbeatType: 'answer',
    autoActivateHeartbeat: false,
    convertImagesToLinks: false,
    noModals: true,
    showLowRepImageUploadWarning: true,
    reputationToPostImages: null,
    bindNavPrevention: true,
    postfix: "",
    imageUploader: {
    brandingHtml: "Powered by u003ca class="icon-imgur-white" href="https://imgur.com/"u003eu003c/au003e",
    contentPolicyHtml: "User contributions licensed under u003ca href="https://creativecommons.org/licenses/by-sa/3.0/"u003ecc by-sa 3.0 with attribution requiredu003c/au003e u003ca href="https://stackoverflow.com/legal/content-policy"u003e(content policy)u003c/au003e",
    allowUrls: true
    },
    noCode: true, onDemand: true,
    discardSelector: ".discard-answer"
    ,immediatelyShowMarkdownHelp:true
    });


    }
    });














    draft saved

    draft discarded


















    StackExchange.ready(
    function () {
    StackExchange.openid.initPostLogin('.new-post-login', 'https%3a%2f%2fdiy.stackexchange.com%2fquestions%2f161054%2fis-fine-stranded-wire-ok-for-main-supply-line%23new-answer', 'question_page');
    }
    );

    Post as a guest















    Required, but never shown

























    4 Answers
    4






    active

    oldest

    votes








    4 Answers
    4






    active

    oldest

    votes









    active

    oldest

    votes






    active

    oldest

    votes









    4














    A terminal problem



    Beyond the potential labeling/marking (or lack thereof) issues with this wire, there is a serious problem with this setup: equipment terminal lugs are not suited for fine stranded wire (anything finer than what UL calls Class C stranding) unless the equipment is specifically listed for use with specific fine strandings, which is not true for light duty loadcenters.



    As a result, what we have right now is a 110.3 violation of the loadcenter's listing and labeling, atop anything else that's going on with the wire itself. Given that the wire appears to be in conduit, simply replacing the run with the correct stuff is the best option, as that will cure any issues with labeling/marking as well, and also gives you the chance to adjust conductor sizing as-needed.






    share|improve this answer
























    • Thank you I was not comfortable with how the lug was capturing the soft bundle of strands now I am certain I will change the cable .

      – Kris
      Apr 2 at 1:51











    • +1 This is the best answer to the headline question and is most likely to help others with the same question in the future.

      – statueuphemism
      Apr 2 at 14:10
















    4














    A terminal problem



    Beyond the potential labeling/marking (or lack thereof) issues with this wire, there is a serious problem with this setup: equipment terminal lugs are not suited for fine stranded wire (anything finer than what UL calls Class C stranding) unless the equipment is specifically listed for use with specific fine strandings, which is not true for light duty loadcenters.



    As a result, what we have right now is a 110.3 violation of the loadcenter's listing and labeling, atop anything else that's going on with the wire itself. Given that the wire appears to be in conduit, simply replacing the run with the correct stuff is the best option, as that will cure any issues with labeling/marking as well, and also gives you the chance to adjust conductor sizing as-needed.






    share|improve this answer
























    • Thank you I was not comfortable with how the lug was capturing the soft bundle of strands now I am certain I will change the cable .

      – Kris
      Apr 2 at 1:51











    • +1 This is the best answer to the headline question and is most likely to help others with the same question in the future.

      – statueuphemism
      Apr 2 at 14:10














    4












    4








    4







    A terminal problem



    Beyond the potential labeling/marking (or lack thereof) issues with this wire, there is a serious problem with this setup: equipment terminal lugs are not suited for fine stranded wire (anything finer than what UL calls Class C stranding) unless the equipment is specifically listed for use with specific fine strandings, which is not true for light duty loadcenters.



    As a result, what we have right now is a 110.3 violation of the loadcenter's listing and labeling, atop anything else that's going on with the wire itself. Given that the wire appears to be in conduit, simply replacing the run with the correct stuff is the best option, as that will cure any issues with labeling/marking as well, and also gives you the chance to adjust conductor sizing as-needed.






    share|improve this answer













    A terminal problem



    Beyond the potential labeling/marking (or lack thereof) issues with this wire, there is a serious problem with this setup: equipment terminal lugs are not suited for fine stranded wire (anything finer than what UL calls Class C stranding) unless the equipment is specifically listed for use with specific fine strandings, which is not true for light duty loadcenters.



    As a result, what we have right now is a 110.3 violation of the loadcenter's listing and labeling, atop anything else that's going on with the wire itself. Given that the wire appears to be in conduit, simply replacing the run with the correct stuff is the best option, as that will cure any issues with labeling/marking as well, and also gives you the chance to adjust conductor sizing as-needed.







    share|improve this answer












    share|improve this answer



    share|improve this answer










    answered Apr 2 at 1:46









    ThreePhaseEelThreePhaseEel

    32.9k115198




    32.9k115198













    • Thank you I was not comfortable with how the lug was capturing the soft bundle of strands now I am certain I will change the cable .

      – Kris
      Apr 2 at 1:51











    • +1 This is the best answer to the headline question and is most likely to help others with the same question in the future.

      – statueuphemism
      Apr 2 at 14:10



















    • Thank you I was not comfortable with how the lug was capturing the soft bundle of strands now I am certain I will change the cable .

      – Kris
      Apr 2 at 1:51











    • +1 This is the best answer to the headline question and is most likely to help others with the same question in the future.

      – statueuphemism
      Apr 2 at 14:10

















    Thank you I was not comfortable with how the lug was capturing the soft bundle of strands now I am certain I will change the cable .

    – Kris
    Apr 2 at 1:51





    Thank you I was not comfortable with how the lug was capturing the soft bundle of strands now I am certain I will change the cable .

    – Kris
    Apr 2 at 1:51













    +1 This is the best answer to the headline question and is most likely to help others with the same question in the future.

    – statueuphemism
    Apr 2 at 14:10





    +1 This is the best answer to the headline question and is most likely to help others with the same question in the future.

    – statueuphemism
    Apr 2 at 14:10













    7














    I can call it right now.



    I don't see any markings on the wires. Now, perhaps the wires come out of a multiconductor cable, whose cable sheath has markings that indicate it is one of the NEC/UL rated types of wire legal for mains wiring. But if not...



    Wires without insulation markings are no wires at all.



    You don't even know what you're looking at here. You don't know what insulation temp column you should be pulling out of for 310.15(B)(16). You don't know if it's 600V insulation. We don't know if the insulation will hold up over time, in the environmental conditions, or with the heat of the wires working normally. For all we know it could be Chinese car battery cable.



    Given that it's all 4 colors, there's a fair chance it's cable in sheath, or was shucked from cable in sheath (there go the markings). This is why you can't shuck NM to get wires for running in conduit.






    share|improve this answer



















    • 1





      We do know it has held up over time since the original setup of mobile home was in 1969. What I don’t know is if it will hold up in the future with a heat pump being added to the mix. There was no ac in this house only a small electric furnace which was rarely used since it is a summer destination. I’m thinking I will replace the short run from outside disconnect to panel.

      – Kris
      Mar 31 at 23:47











    • Is there an NEC/UL rated wire that is fine stranded and legal for use as service entrance cable?

      – Kris
      Mar 31 at 23:58
















    7














    I can call it right now.



    I don't see any markings on the wires. Now, perhaps the wires come out of a multiconductor cable, whose cable sheath has markings that indicate it is one of the NEC/UL rated types of wire legal for mains wiring. But if not...



    Wires without insulation markings are no wires at all.



    You don't even know what you're looking at here. You don't know what insulation temp column you should be pulling out of for 310.15(B)(16). You don't know if it's 600V insulation. We don't know if the insulation will hold up over time, in the environmental conditions, or with the heat of the wires working normally. For all we know it could be Chinese car battery cable.



    Given that it's all 4 colors, there's a fair chance it's cable in sheath, or was shucked from cable in sheath (there go the markings). This is why you can't shuck NM to get wires for running in conduit.






    share|improve this answer



















    • 1





      We do know it has held up over time since the original setup of mobile home was in 1969. What I don’t know is if it will hold up in the future with a heat pump being added to the mix. There was no ac in this house only a small electric furnace which was rarely used since it is a summer destination. I’m thinking I will replace the short run from outside disconnect to panel.

      – Kris
      Mar 31 at 23:47











    • Is there an NEC/UL rated wire that is fine stranded and legal for use as service entrance cable?

      – Kris
      Mar 31 at 23:58














    7












    7








    7







    I can call it right now.



    I don't see any markings on the wires. Now, perhaps the wires come out of a multiconductor cable, whose cable sheath has markings that indicate it is one of the NEC/UL rated types of wire legal for mains wiring. But if not...



    Wires without insulation markings are no wires at all.



    You don't even know what you're looking at here. You don't know what insulation temp column you should be pulling out of for 310.15(B)(16). You don't know if it's 600V insulation. We don't know if the insulation will hold up over time, in the environmental conditions, or with the heat of the wires working normally. For all we know it could be Chinese car battery cable.



    Given that it's all 4 colors, there's a fair chance it's cable in sheath, or was shucked from cable in sheath (there go the markings). This is why you can't shuck NM to get wires for running in conduit.






    share|improve this answer













    I can call it right now.



    I don't see any markings on the wires. Now, perhaps the wires come out of a multiconductor cable, whose cable sheath has markings that indicate it is one of the NEC/UL rated types of wire legal for mains wiring. But if not...



    Wires without insulation markings are no wires at all.



    You don't even know what you're looking at here. You don't know what insulation temp column you should be pulling out of for 310.15(B)(16). You don't know if it's 600V insulation. We don't know if the insulation will hold up over time, in the environmental conditions, or with the heat of the wires working normally. For all we know it could be Chinese car battery cable.



    Given that it's all 4 colors, there's a fair chance it's cable in sheath, or was shucked from cable in sheath (there go the markings). This is why you can't shuck NM to get wires for running in conduit.







    share|improve this answer












    share|improve this answer



    share|improve this answer










    answered Mar 31 at 23:35









    HarperHarper

    75.9k449153




    75.9k449153








    • 1





      We do know it has held up over time since the original setup of mobile home was in 1969. What I don’t know is if it will hold up in the future with a heat pump being added to the mix. There was no ac in this house only a small electric furnace which was rarely used since it is a summer destination. I’m thinking I will replace the short run from outside disconnect to panel.

      – Kris
      Mar 31 at 23:47











    • Is there an NEC/UL rated wire that is fine stranded and legal for use as service entrance cable?

      – Kris
      Mar 31 at 23:58














    • 1





      We do know it has held up over time since the original setup of mobile home was in 1969. What I don’t know is if it will hold up in the future with a heat pump being added to the mix. There was no ac in this house only a small electric furnace which was rarely used since it is a summer destination. I’m thinking I will replace the short run from outside disconnect to panel.

      – Kris
      Mar 31 at 23:47











    • Is there an NEC/UL rated wire that is fine stranded and legal for use as service entrance cable?

      – Kris
      Mar 31 at 23:58








    1




    1





    We do know it has held up over time since the original setup of mobile home was in 1969. What I don’t know is if it will hold up in the future with a heat pump being added to the mix. There was no ac in this house only a small electric furnace which was rarely used since it is a summer destination. I’m thinking I will replace the short run from outside disconnect to panel.

    – Kris
    Mar 31 at 23:47





    We do know it has held up over time since the original setup of mobile home was in 1969. What I don’t know is if it will hold up in the future with a heat pump being added to the mix. There was no ac in this house only a small electric furnace which was rarely used since it is a summer destination. I’m thinking I will replace the short run from outside disconnect to panel.

    – Kris
    Mar 31 at 23:47













    Is there an NEC/UL rated wire that is fine stranded and legal for use as service entrance cable?

    – Kris
    Mar 31 at 23:58





    Is there an NEC/UL rated wire that is fine stranded and legal for use as service entrance cable?

    – Kris
    Mar 31 at 23:58











    1














    Yes there is fine stranded wire, it is not common because it is more expensive. I use it on equipment that has a high vibration or regular movement because the fine wire holds up better in those conditions than heavier strands. thick strands tend to break with movement. Since this is a mobile that might be why this type wire was used but it goes back to the size of the wire if it will do the job or not, fine or heavy strands don't matter it's the gauge or size that is the limiting factor.






    share|improve this answer
























    • I’m thinking grand dad who had a big woodworking shop with some large three phase machines may have used some reclaimed wire here. I will verify the size of the wire before final decision is made to replace or not.

      – Kris
      Apr 1 at 14:29
















    1














    Yes there is fine stranded wire, it is not common because it is more expensive. I use it on equipment that has a high vibration or regular movement because the fine wire holds up better in those conditions than heavier strands. thick strands tend to break with movement. Since this is a mobile that might be why this type wire was used but it goes back to the size of the wire if it will do the job or not, fine or heavy strands don't matter it's the gauge or size that is the limiting factor.






    share|improve this answer
























    • I’m thinking grand dad who had a big woodworking shop with some large three phase machines may have used some reclaimed wire here. I will verify the size of the wire before final decision is made to replace or not.

      – Kris
      Apr 1 at 14:29














    1












    1








    1







    Yes there is fine stranded wire, it is not common because it is more expensive. I use it on equipment that has a high vibration or regular movement because the fine wire holds up better in those conditions than heavier strands. thick strands tend to break with movement. Since this is a mobile that might be why this type wire was used but it goes back to the size of the wire if it will do the job or not, fine or heavy strands don't matter it's the gauge or size that is the limiting factor.






    share|improve this answer













    Yes there is fine stranded wire, it is not common because it is more expensive. I use it on equipment that has a high vibration or regular movement because the fine wire holds up better in those conditions than heavier strands. thick strands tend to break with movement. Since this is a mobile that might be why this type wire was used but it goes back to the size of the wire if it will do the job or not, fine or heavy strands don't matter it's the gauge or size that is the limiting factor.







    share|improve this answer












    share|improve this answer



    share|improve this answer










    answered Apr 1 at 14:09









    Ed BealEd Beal

    34.7k12148




    34.7k12148













    • I’m thinking grand dad who had a big woodworking shop with some large three phase machines may have used some reclaimed wire here. I will verify the size of the wire before final decision is made to replace or not.

      – Kris
      Apr 1 at 14:29



















    • I’m thinking grand dad who had a big woodworking shop with some large three phase machines may have used some reclaimed wire here. I will verify the size of the wire before final decision is made to replace or not.

      – Kris
      Apr 1 at 14:29

















    I’m thinking grand dad who had a big woodworking shop with some large three phase machines may have used some reclaimed wire here. I will verify the size of the wire before final decision is made to replace or not.

    – Kris
    Apr 1 at 14:29





    I’m thinking grand dad who had a big woodworking shop with some large three phase machines may have used some reclaimed wire here. I will verify the size of the wire before final decision is made to replace or not.

    – Kris
    Apr 1 at 14:29











    1














    I won't comment on the legalities since I'm not from the US and I'm not deeply familiar with their codes, but from a safety point of view my big concern would be the insulation.



    It's difficult to be 100% sure from a photo but those conductors look like rubber to me. Rubber insulation was phased out from fixed-wiring wires/cables a long time ago, but it's still used to this day on some types of flexible cord.



    The problem with rubber is it can oxidise over time leading it to harden, then when the cables are manipulated to modify the installation it can crack.






    share|improve this answer




























      1














      I won't comment on the legalities since I'm not from the US and I'm not deeply familiar with their codes, but from a safety point of view my big concern would be the insulation.



      It's difficult to be 100% sure from a photo but those conductors look like rubber to me. Rubber insulation was phased out from fixed-wiring wires/cables a long time ago, but it's still used to this day on some types of flexible cord.



      The problem with rubber is it can oxidise over time leading it to harden, then when the cables are manipulated to modify the installation it can crack.






      share|improve this answer


























        1












        1








        1







        I won't comment on the legalities since I'm not from the US and I'm not deeply familiar with their codes, but from a safety point of view my big concern would be the insulation.



        It's difficult to be 100% sure from a photo but those conductors look like rubber to me. Rubber insulation was phased out from fixed-wiring wires/cables a long time ago, but it's still used to this day on some types of flexible cord.



        The problem with rubber is it can oxidise over time leading it to harden, then when the cables are manipulated to modify the installation it can crack.






        share|improve this answer













        I won't comment on the legalities since I'm not from the US and I'm not deeply familiar with their codes, but from a safety point of view my big concern would be the insulation.



        It's difficult to be 100% sure from a photo but those conductors look like rubber to me. Rubber insulation was phased out from fixed-wiring wires/cables a long time ago, but it's still used to this day on some types of flexible cord.



        The problem with rubber is it can oxidise over time leading it to harden, then when the cables are manipulated to modify the installation it can crack.







        share|improve this answer












        share|improve this answer



        share|improve this answer










        answered Apr 1 at 15:19









        Peter GreenPeter Green

        2,136616




        2,136616






























            draft saved

            draft discarded




















































            Thanks for contributing an answer to Home Improvement Stack Exchange!


            • Please be sure to answer the question. Provide details and share your research!

            But avoid



            • Asking for help, clarification, or responding to other answers.

            • Making statements based on opinion; back them up with references or personal experience.


            To learn more, see our tips on writing great answers.




            draft saved


            draft discarded














            StackExchange.ready(
            function () {
            StackExchange.openid.initPostLogin('.new-post-login', 'https%3a%2f%2fdiy.stackexchange.com%2fquestions%2f161054%2fis-fine-stranded-wire-ok-for-main-supply-line%23new-answer', 'question_page');
            }
            );

            Post as a guest















            Required, but never shown





















































            Required, but never shown














            Required, but never shown












            Required, but never shown







            Required, but never shown

































            Required, but never shown














            Required, but never shown












            Required, but never shown







            Required, but never shown







            Popular posts from this blog

            Plaza Victoria

            In PowerPoint, is there a keyboard shortcut for bulleted / numbered list?

            How to put 3 figures in Latex with 2 figures side by side and 1 below these side by side images but in...